3c3a4ac517
Why I did it The sensors and sensord processes were reporting data on unused sensors. This lead to ALARM messages or erroneous values that could be misinterpreted. How I did it Ignore the affected sensors in the sensors.conf How to verify it Check that there are no longer ALARM messages from sensord in the syslog or in the output of sensors
50 lines
1.2 KiB
Plaintext
50 lines
1.2 KiB
Plaintext
# libsensors configuration file for DCS-7050QX-32S
|
|
# ------------------------------------------------
|
|
#
|
|
|
|
bus "i2c-2" "SCD 0000:02:00.0 SMBus master 0 bus 0"
|
|
bus "i2c-3" "SCD 0000:02:00.0 SMBus master 0 bus 1"
|
|
bus "i2c-5" "SCD 0000:02:00.0 SMBus master 0 bus 3"
|
|
bus "i2c-6" "SCD 0000:02:00.0 SMBus master 0 bus 4"
|
|
bus "i2c-7" "SCD 0000:02:00.0 SMBus master 0 bus 5"
|
|
|
|
chip "k10temp-pci-00c3"
|
|
label temp1 "Cpu temp sensor"
|
|
|
|
chip "fam15h_power-pci-00c4"
|
|
ignore power1
|
|
|
|
chip "max6658-i2c-2-4c"
|
|
label temp1 "Board temp sensor"
|
|
set temp1_max 55
|
|
set temp1_crit 70
|
|
|
|
label temp2 "Front panel temp sensor"
|
|
set temp2_max 65
|
|
set temp2_crit 75
|
|
|
|
chip "max6658-i2c-3-4c"
|
|
label temp1 "Cpu board temp sensor"
|
|
set temp1_max 75
|
|
set temp1_crit 80
|
|
|
|
label temp2 "Back panel temp sensor"
|
|
set temp2_max 75
|
|
set temp2_crit 80
|
|
|
|
chip "pmbus-i2c-6-58"
|
|
label temp1 "Power supply 1 hotspot sensor"
|
|
label temp2 "Power supply 1 inlet temp sensor"
|
|
label temp3 "Power supply 1 sensor"
|
|
|
|
ignore fan2
|
|
ignore fan3
|
|
|
|
chip "pmbus-i2c-5-58"
|
|
label temp1 "Power supply 2 hotspot sensor"
|
|
label temp2 "Power supply 2 inlet temp sensor"
|
|
label temp3 "Power supply 2 sensor"
|
|
|
|
ignore fan2
|
|
ignore fan3
|